| Equipment |
Class
A- Less then 16 feet
(less than 4.9m) |
Class 1-
16
feet to less than 26 feet
(4.9 to less than 7.9m) |
Class
2- 26 to less than 40 feet
(7.9 to less than 7.9m) |
Class 3-
40 to less than 65 feet
(12.2 to less than 19.8m) |
Backfire Flame Arrestor |
One approved
device on each carburetor
of all gasoline engines
installed after April 25,
1940, except outboard motors. |
Ventilation- Boats
built before Aug. 1, 1980 |
At least
two ventilator ducts
filled with cowls or
their equivalent for
the purpose of properly
and effectively ventilating
the bilges of every closed
engine and fuel tank
compartment of boats
constructed or decked
over after April 25,
1940, using gasoline
as fuel or other fuels
having a flash point
of 110° or less |
Ventilation Boats
built on or after Aug.
1, 1980 |
At least
two ventilator ducts
for the purpose of efficiently
ventilating every closed
compartment that contains
a gasoline engine and
every close compartment
containing a gasoline
tank, except those having
permanently installed
tanks which vent outside
the boat and which contain
no unprotected electrical
devices. Also, engine
compartments containing
a gasoline engine having
a cranking motor must
contain power operated
exhaust blowers which
can be controlled from
the instrument panel. |
Personal Flotation Devices |
One approved Type I,
II, II, or V PFD for each
person on board or being
towed on water skies, ect. |
One approved
Type I, II, III, or V PFD
for each person on board
or being towed on water
skis, ect; and, in addition,
one throwable type IV device. |
Bell, Whistle |
Every
vessel less than 12 meters
(39.4 feet) must carry
an efficient sound producing
device. |
Every vessel
12 meters (39.4 feet) but
less than 20 meters (65.5
feet) in length must carry
a whistle and a bell. The
bell must be audible 1/2
nautical mile. The mouth
of the bell must be at
least 200mm (7.87 inches)
in diameter. |
Visual
Distress Signals Required on coastal waters
only
|
Must carry approved
visual distress signals
for night time use. |
Must carry visual distress
signals approved for both
daytime use and night time
use. Note: all boats carrying
six or more passengers
for hire must meet these
requirements. |
Fire
Extinguishers (Must say Coast Guard-
Approved) |
At least
on B-1 type approved hard
portable fire extinguisher.
Not required on outboard
motorboats less than 26
feet (7.9 meters) in length
and not carrying passengers
to hire if the construction
of such motorboat will
not permit the entrapment
of explosive or flammable
gases or vapors and if
fuel tanks are not permanently
installed. |
At least two B-1 type
approved portable fire
extinguishers; OR at least
one B-2 type approved portable
fire extinguisher. |
At least three B-1
type approved portable
fire extinguishers; OR
at least one B-1 type
plus one B-2 type approved
portable fire extinguisher. |
NOTE:
When a fixed fire extinguisher
system is installed in
the machinery space(s),
it will replace one B-1
type portable extinguisher. |